Chauvin Arnoux B102 Current Clamp, AC Adapter, 400A ac AC Max, Current Output - P01120083
The B102 Current Clamp accurately measures leakage currents up to 400A AC, ensuring safety without equipment disconnection.
Manufacturer part number: P01120083
GTIN: 3760171412657
Adapter Type = AC
Maximum AC Current = 400A ac
Best Accuracy = = 0.35 %
Maximum Conductor Size = 115mm
Safety Category = CAT III 600 V, CAT IV 300V
Output Type = Current
Connector Type = 4 mm Plug
Cable Length Extended = 1.5m
Maximum Operating Temperature = +55°C
Minimum Operating Temperature = -10°C
Safety Category Level = CAT III, CAT IVV
B102 Leakage Current Clamp. The B102 current clamp is designed for measuring leakage current diverted towards the earth. It enables the fault to be located or anticipated without disconnecting the equipment linked. The current clamp is specially designed to detect low fault currents on power circuits. The measurements can be made on any type of installation: single-phase, 3 or 4 wire threephase, balanced or not, with the neutral grounded earth or impedant Differential or leakage current, from 500 µA Current up to 400 A max 2 measurement ranges: 4 A AC / 400 A AC Bandwidth: 48 Hz to 1000 Hz Output: 1.5 m cord with double insulation having male safety plugs 4mm in diameter